Theory of Operation
2
16
The following diagram shows the suggested external connection to external equipment.
Figure 4. Relay output connection—External connection to external equipment
Connect Reset inputs in parallel
The Telco alarm reset inputs of a redundant pair of SPMs can be connected in parallel such that
both SPMs will receive a reset signal independent of the other. The connection scheme is based
on the following:
1. External reset sources will produce a DC voltage to reset the associated alarms.
2. The SPM reset inputs are isolated from each other and do not change DC loading based on
the power or operational state of the SPM.
The following diagram shows the suggested external connection to external equipment.
COM
NC
NO
}
Closes during
minor alarm
10
9
8
COM
NC
NO
}
Closes during
major alarm
13
12
11
COM
NC
NO
}
Closes during
critical alarm
7
6
5
COM
NO
}
Closes when
power is
applied
15
14
COM
NC
NO
10
9
8
COM
NC
NO
13
12
11
COM
NC
NO
7
6
5
COM
NO
15
14
SPM 1
SPM 2